dc.description.abstractThis paper proposes a simple yet effective Distribution Phasor Measurements based Islanding Detector (DPMID). The proposed detector relies on the voltage phasor measurements, obtained from the Phasor Measurement Unit (PMU), deployed at the respective Distributed Generator (DG) bus. Next, Teager-Kaiser energy of the positive sequence voltage is readily computed, which effectively discriminates the islanding scenarios from other nonislanding scenarios. The efficacy of the proposed method is verified through various PSCAD/EMTDC simulation, and Hardware-In-Loop (HIL) experiment using Real-Time Digital Simulator (RTDS) and DS1104 microcontroller. A detailed comparative assessment of the proposed method (PM) with recent islanding detection techniques preceded by online signal parameter estimation demonstrates the superiority of the PM with respect to various islanding detection standard such as IEEE 1547–2018, UL1741-SA.en_US
dc.language.isoen_USen_US
dc.subjectTeager-Kaiser energyen_US
dc.subjectPhasor measurement uniten_US
dc.subjectIslanding detection techniqueen_US
dc.subjectDistributed generationen_US
dc.subjectReal time digital simulatoren_US
dc.subjectDS1104en_US
dc.titleA distribution-level PMU enabled Teager-Kaiser energy based islanding detectoren_US