Please use this identifier to cite or link to this item:
http://dspace.iitrpr.ac.in:8080/xmlui/handle/123456789/1809
Title: | Placement of distribution-level phasor measurements for topological observability and monitoring of active distribution networks |
Authors: | Chauhan, K. Sodhi, R. |
Keywords: | Active distribution network (ADN) distribution-level phasor measurement unit (D-PMU) integer linear programming (ILP) state estimation (SE) topological observability. |
Issue Date: | 13-Jun-2021 |
Abstract: | This article presents a new method for the placement of distribution-level phasor measurement units (D-PMUs) in the active distribution networks (ADNs). The new objective function and constraints are proposed to ensure the minimization of capital cost as well the maximization of system observability, in the presence of distributed generations (DGs), zero injection buses (ZIBs), and tie-switches. The integer linear programming (ILP) is used to solve the framed objective function and the constraints. Furthermore, the accuracy of ADN state estimation (ADN-SE), in various system conditions, such as network reconfiguration, change in load demand, and measurement error degradation, is analyzed to check the impact of the proposed placement. The uncertainties caused by D-PMUs, DGs, and pseudomeasurements are considered well in ADN-SE using Monte Carlo simulations. The IEEE 69, 123, Indian 85, and UKGDS 95 bus distribution systems are used in the case studies. |
URI: | http://localhost:8080/xmlui/handle/123456789/1809 |
Appears in Collections: | Year-2020 |
Files in This Item:
File | Description | Size | Format | |
---|---|---|---|---|
Fulltext.pdf | 1.77 MB | Adobe PDF | View/Open Request a copy |
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.