Please use this identifier to cite or link to this item: http://dspace.iitrpr.ac.in:8080/xmlui/handle/123456789/2817
Full metadata record
DC FieldValueLanguage
dc.contributor.authorSingla, R. K.-
dc.contributor.authorDas, R.-
dc.date.accessioned2021-09-29T17:12:53Z-
dc.date.available2021-09-29T17:12:53Z-
dc.date.issued2021-09-29-
dc.identifier.urihttp://localhost:8080/xmlui/handle/123456789/2817-
dc.description.abstractIn this work, application of the Golden Section Search Method (GSSM) is illustrated to inversely retrieve the controlling parameter meeting a desired performance requirement in an induced draft cooling tower. Merkel number is an important performance parameter because it involves various parameters such as global heat and mass transfer coefficient, water flow rate, dimensions (interfacial area per unit volume) and range within itself. At first, experiments have been performed to get accurate correlations for Merkel number against the controlling parameter that is required to be estimated, which is the air mass flow rate. Then, an inverse optimization technique involving GSSM has been used to estimate the required air flow rate in order to satisfy a given performance parameter. It is found from the present study that the controlling parameter estimated using GSSM yields a very good reconstruction of the Merkel number.en_US
dc.language.isoen_USen_US
dc.subjectGSSMen_US
dc.subjectinduced draft cooling toweren_US
dc.subjectinverse optimizationen_US
dc.subjectMerkel numberen_US
dc.titleRetrieval of controlling parameter in induced draft cooling tower using inverse methoden_US
dc.typeArticleen_US
Appears in Collections:Year-2016