INSTITUTIONAL DIGITAL REPOSITORY

Investigation of limitations in active damping control of LCL filter resonance using inverter side current feedback in grid connected voltage source converter

Show simple item record

dc.contributor.author Muddasani, S.
dc.contributor.author Teja, A. V. R.
dc.date.accessioned 2021-07-24T11:47:55Z
dc.date.available 2021-07-24T11:47:55Z
dc.date.issued 2021-07-24
dc.identifier.uri http://localhost:8080/xmlui/handle/123456789/2208
dc.description.abstract This paper investigates the active damping of LCL filter resonance in a grid connected voltage source inverter. The active damping realized using feedback of inverter side current is considered for analysis. A detailed study showing suitable choice of resistor required for resonance damping in case of the passive and active damping methods is presented. An explicit study showing the limitations of active damping over passive damping for a chosen Switching and resonance frequencies has carried out. The proposed work is simulated using MATLAB/Simulink for the resonance frequency of 1.4kHz and switching frequency of 10KHz. Typical results are reported and analyzed. It is observed from results that the virtual resistor introduced using active damping technique is unlike to the passive damping after a point of Rd values. This issue can be resolved by choosing controller bandwidth adaptive to the changes present in value of virtual resistor. en_US
dc.language.iso en_US en_US
dc.subject Passive damping (PD) en_US
dc.subject Active damping (AD) en_US
dc.subject LCL filter en_US
dc.subject grid connected inverters en_US
dc.subject single phase system en_US
dc.title Investigation of limitations in active damping control of LCL filter resonance using inverter side current feedback in grid connected voltage source converter en_US
dc.type Article en_US